Permit: T07PL00380

Parcel: 127050500


Addresses:

4741 E 3RD ST

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
03/28/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
03/20/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
YARDWATER IS INSTALLED W/ONLY 10" OR LESS
FROM TOP OF PIPE TO GRADE
PROVIDE 12" MIN. COVER
PROTECT COPPER 90 DEG. TOUCHING CONCRETE
03/07/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
AFTER HRS. INSP. REQUESTED BY BECKY
PAID W/CHECK #1017
STARR PASS PIPELINE

YARD WATER FROM M TO FRONT OF HOUSE IS OK TO COVER
CORRECT PIPING IN SIDE YARD.
03/07/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEWER NOT YET INSTALLED
PROVIDE PLAN
PROVIDE RIGHT OF WAY PERMIT
12" OF COVER REQUIRED
HORIZONTAL PVC CANNOT BE EXPOSED - 313.4 158
316.1.6 PVC PRIMER SHALL BE USED AND SHALL BE VISIBLE
HB VAC BREAKERS REQUIRED - 316.1.1.4
301.1.2.4.2