Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/02/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE PROOF OF MECHANICAL INSPECTION |
|
| 02/27/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* ALL CORRECTIONS EXCEPT FOR UNIT A, FAV HAVE BEEN CORRECTED. NEED TO SEAL WALL PENETRATIONS UTILITY CLEARANCE GIVEN FOR UNITS B, C, D AND UTILITY RM UNIT A; PERMIT REQUIRED ON NEW UNIT EVEN IF IT WAS INSTALLED BY PREVIOUS OWNER. |
|
| 02/23/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT A - HAVE A RELATIVELY NEW FAV PLEASE PROVIDE INSPECTION HISTORY FOR UNIT CONDENSATE PIPED TO SEWER VENT SEDIMENT TRAP ON GAS LINE REQUIRED UNIT D REPLACE DAMAGED PIPE. WATER HEATER VENT HAS BACKPITCH VENT TEE NOT CORRECTLY SIZED FOR TWO 4" VENTS WH T&P'S SHALL TERMINATE OUTSIDE OF BUILDING FLEX NOT ALLOWED SUPPORT BELOW GRADE PIPING SEAL WALL PENETRATIONS PSI TEST ABC AND UTILITY PVC OK |