Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* #227-07 |
|
| 02/26/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/4" GAS PIPE SUPPLYING 107,000 BTU AT APPX 12O' IS UNDERSIZED PER TABLE 12-7 2003 UPC 2. 12" COVER REQUIRED, LEAVE PIPING EXPOSED FOR INSP. 3. USE CORRECT SIZE STRUT CLAMPS AND REMOVE SHARP BURRS FROM UNISTRUT. 4. REMOVE TAPE FROM CONNECTION TO DOUBLE WALL VENT 5. SECURE W/SCREWS 6. PROVIDE PETITION OF APPEAL 7. OBTAIN PERMIT FOR YARD WATER 8. INSTALL HB VACUUM BREAKERS. |