Permit: T07PL00339

Parcel: 121090380


Addresses:

5313 E LINDEN PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
#22507
02/21/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE WH VENT W/GALV SCREWS
2. BOND GAS PIPING TO WATER
3. NEED SEDIMENT TRAPS AT WH & FURNACE
4. T&P DRAIN CANNOT TRAP WATER, IT MUST GRAVITY DRAIN
5. OBTAIN PETITION OF APPEAL FOR WH DRAIN FROM PERMIT COUNTER.
6. INSTALL DRAIN PAN AND EXTERIOR PRV (125 PSI)

TEST OK, OK TO COVER YARD PIPING.