Permit: T07PL00322

Parcel: 112051110

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
03/20/2007 PLUMBING - FINAL Cancelled
03/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/12/2007 PLUMBING - FINAL Cancelled
03/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/01/2007 PLUMBING - FINAL Cancelled CANCELLED PER MIKE
02/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTINUED NOT READY WILL RESULT IN A REINSPECTION FEE
FAV ALSO REQUIRES A SEDIMENT TRAP
02/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. ROOF FLASHINGS TO BE MADE WATER TIGHT.
2. PIPING ON ROOF TO BE MINIMUM 3 1/2" ABOVE ROOF AND SUPPORTED AT CORRECT INTERVALS WITH BLOCKING MASTICED TO ROOF.
3. WATER HEATER T&P DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT.
4. GAS PIPING IS UNDERSIZED PROVIDE CORRECTLY SIZED GAS SYSTEM FOR 205,000 BTU DEMAND AT 50'
5. PROVIDE UPPER COMBUSTION AIR OPENING FROM OUTSIDE SOURCE EQUAL TO 40,000 BTU DEMAND FOR WATER HEATER
6. SECURE GAS AT STOVE