Permit: T07PL00305

Parcel: 112051140

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/26/2007 PLUMBING - FINAL Approved
03/20/2007 PLUMBING - FINAL Cancelled
03/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/09/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE PIPING IN WALL AT STOVE AS REQUESTED ON 2/14
2. USE A CRIMP TOOL TO MAKE A CRIMP JOINT ON SINGLE WALL METAL VENT PIPING.
3. REPLACE DAMAGED PIECE
4. PROVIDE 1" OF CLEARANCE BETWEEN B VENT AND WOOD AT ROOF PENETRATION
5. INSTALL A ROOF FLASHING ON VENT
6. VENT COLLARS ARE FOR USE AT CEILING PENETRATION
7. TERMINATE T&P W/OUT THREADS
03/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/01/2007 PLUMBING - FINAL Cancelled CANCELLED PER MIKE MULLET
02/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. WH; VENT & T&P
2. DROP UNDER STRAIN, SWING JOINT SHOULD HAVE BEEN USED TO COMPENSATE FOR SLOPE OF ROOF.
3. SECURE DROP AT STOVE.
4. PROVIDE ACCESS TO ROOF.
02/13/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*