Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2007 | PLUMBING - FINAL | Approved | ||
| 03/20/2007 | PLUMBING - FINAL | Cancelled | ||
| 03/19/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/09/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE PIPING IN WALL AT STOVE AS REQUESTED ON 2/14 2. USE A CRIMP TOOL TO MAKE A CRIMP JOINT ON SINGLE WALL METAL VENT PIPING. 3. REPLACE DAMAGED PIECE 4. PROVIDE 1" OF CLEARANCE BETWEEN B VENT AND WOOD AT ROOF PENETRATION 5. INSTALL A ROOF FLASHING ON VENT 6. VENT COLLARS ARE FOR USE AT CEILING PENETRATION 7. TERMINATE T&P W/OUT THREADS |
|
| 03/05/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/01/2007 | PLUMBING - FINAL | Cancelled | CANCELLED PER MIKE MULLET | |
| 02/21/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WH; VENT & T&P 2. DROP UNDER STRAIN, SWING JOINT SHOULD HAVE BEEN USED TO COMPENSATE FOR SLOPE OF ROOF. 3. SECURE DROP AT STOVE. 4. PROVIDE ACCESS TO ROOF. |
|
| 02/13/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |