Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/01/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. WAITED FOR A LADDER TO INSPECT ABOVE CEILING. 2. SUPPORT HORIZONTAL DRAIN LINE W/PIPE SUPPORT. 3. PREVIOUS INSPECTION WAS FOR AN EXPIRED PERMIT FROM 2000 THAT NEEDS TO BE FINALED. 4. PLEASE CALL FOR INSPECTION FOR OPEN ACTIVITY FROM 2000 AND PROVIDE ANY INSPECTION HISTORY. 5. TEMP CAPS HAVE BEEN INSTALLED, NO OBVIOUS PLUMBING HAZARDS EXIST. 6. WC AND LAV MAY NOT MEET ACCESSIBILITY REQUIREMENTS CALL FOR BUILDING INSPECTION. |
|
| 02/26/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SOME FIXTURES HAVE BEEN REMOVED. 2. TEMPORARILY CAP ANY OPEN SEWER PIPES. 3. AT SOUTH EASTERN SECTION OF SUITE TWO RMS W/SINK PIPING PER PLAN DATED 5/30/00; OVERHEAD PIPING NEEDS TO BE PROPERLY SUPPORTED. FIXTURES HAVE BEEN REMOVED. 4. ALL FIXTURES NEED TO BE INSTALLED OR WATER & DRAIN PIPING WOULD NEED TO BE PERM CAPPED. 5. FACILITY MANAGEMENT OR RESPONSIBLE PARTY NEEDS TO SCHEDULE AN INSPECTION AND PROVIDE ANY PREVIOUS INSP. HISTORY. 6. I BELIEVE THAT THERE IS ALSO AN OPEN WATER HEATER PERMIT. WATER HEATER ABV CEILING REQUIRES A DRAIN TO EXTERIOR. |
|
| 02/15/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* T&P DRAIN & DRAIN PAN CANNOT COMBINE PIPE T&P TO EXTERIOR SEPARATELY FLEX NOT ALLOWED ON T&P SUPPORT DRAIN LINES LEAVE A CONTACT NUMBER |