Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER SW GAS 889-1888 |
|
| 02/12/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TEST SHALL HOLD MINIMUM PRESSURE WITH NO LOSS OF PRESSURE. 2. PROVIDE UPPER COMBUSTION AIR OPENING EQUAL TO 1" SQ. INCHES PER EVERY 3000 BTU OF TOTAL BTU'S OF WATER HEATER & FURNACE 132,000 BTU 3. REMOVE COMBUSTIBLE MATERIAL FROM DOUBLE WALL VENT AT CEILING LEVEL. |