Permit: T07PL00284

Parcel: 127081710


Addresses:

5433 E 10TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/15/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD ON PIPE AT METER
02/14/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 1/2" NOT LARGE ENOUGH FOR 100,000 BTU FURNACE
(NOTE: ORIGINAL PIPE IS 3/4")
2. RUN 3/4" TO FURNACE AS CLOSE AS POSSIBLE TO CONNECTION.
3. RETEST PIPING.
4. SECURE PIPE DROP AT TRANSITION TO CSST IN WALL
5. 1/2" TO DRYER IS UNDER STRAIN, USE SWING JOINT TO ACCOMODATE SLOPE OF ROOF.
6. SEDIMENT TRAPS REQUIRED AT WH & FURNACE
7. SECURE VENT CONNECTOR W/GALV SHEET METAL SCREWS
REMOVE TAPE AT CONNECTION TO DOUBLE WALL
INSTALL LISTED TYPE B VENT CAP AT WH VENT
8. BOND TO CW BEFORE DIELECTRIC FITTING AT WH
9. YARD PIPING W/TEST OK TO COVER