Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/05/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) OK FOR GAS AFTER COMPLETING THE FOLLOWING CORRECTIONS 2) PROVIDE 1" CLEARANCE BETWEEN B-VENT AND WOOD AT WH VENT 3) PROVIDE MINIMUM 1 1/2" CLEARANCE BETWEEN PIPE AND ROOF 4) INSTALL SEDIMENT TRAPS AT WH AND FURNACE 5) REMOVE SHARP BURR FROM STRUT 6) GAS CLEARANCE GIVEN 7) RECALL FOR FINAL INSPECTION 03090 |