Permit: T07PL00236

Parcel: 127021630


Addresses:

5447 E 3RD ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/02/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE HOME MADE VENT "T" AT WH/FURNACE, USE LISTED VENT TEE
2) PROVIDE PETITION OF APPEAL FOR WH T & P TERMINATION AND INSTALL EXTERIOR PRV
3) INSTALL SEDIMENT TRAPS AT WH/FURNACE
02/02/2007 PLUMBING - FINAL Partial Approval PETITION OF APPEAL #21707
OK TO TURN ON GAS AFTER CORRECTING VENT
INSTALL 5 X 6 X 3 TEE. CRIMP END GOES UP
SECURE WITH GALV SHEET METAL SCREWS
INSTALL 125 PSI PRESSURE RELIEF VALVE AT EXTERIOR WATER LINE
PAID $108.00 WITH CHECK #592 FOR AFTER HOURS INSP