Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) OK GAS |
|
| 12/21/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE PREVIOUSLY NOTED CORRECTIONS 2) SECURE ALL PIPING AT APPLIANCES 3) SUPPORT PIPING WITH LISTED PIPE SUPPORTS 4) HARD PIPE FROM GAS MAIN BELOW MOBILE HOME TO FURNACE VALVE |
|
| 01/31/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEW YARD PIPING FROM METER TO MOBILE HOME SERVICE IS OK TO COVER. 2. PIPING UNDER HOME SHALL BE PROPERLY SUPPORTED WITH PIPE SUPPORTS SUSPENDED FROM MOBILE HOME. 3. ALL PIPING REQUIRES A PRESSURE TEST. 4. AGA VALVES REQUIRED. 5. REMOVE OLD GREASE COCKS FROM PIPING. 6. PROVIDE COMBUSTION AIR OPENINGS FOR WH 7. GAS VALVE FOR STOVE AND FURNANCE SHALL BE LOCATED IN SAME ROOM AS STOVE AND FURNACE AND WITHIN 4' OF APPLIANCE. |