Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE FOR T&P RELIEF. SHALL PROVIDE PLUG IN DRAIN PAN PROVIDE NIPPLE WITH NO THREADS IN DISCHARGE END OF 125# PRESSURE RELIEF. PROVIDE VACUUM BREAKER FOR NEW HOSE BIB. 2. PROVIDE CORRECT TRANSITION FROM SINGLE WALL VENT TO DOUBLE WALL VENT IN HEATER CLOSET. 3. RE-ATTACH BUILDING GROUND AT WATER SERVICE 4. PROVIDE CORRECT COMBUSTION AIR FOR WATER HEATER. |