Permit: T07PL00155

Parcel: 136332590

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/16/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE FOR T&P RELIEF. SHALL PROVIDE PLUG IN DRAIN PAN
PROVIDE NIPPLE WITH NO THREADS IN DISCHARGE END OF 125# PRESSURE RELIEF. PROVIDE VACUUM BREAKER FOR NEW HOSE BIB.
2. PROVIDE CORRECT TRANSITION FROM SINGLE WALL VENT TO DOUBLE WALL VENT IN HEATER CLOSET.
3. RE-ATTACH BUILDING GROUND AT WATER SERVICE
4. PROVIDE CORRECT COMBUSTION AIR FOR WATER HEATER.