Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07PL00144

Parcel: 12607064D


Addresses:

109 N LONGFELLOW AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/16/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
OK TO CONNECT NEW INSTA HOT TO EXISTING GAS SYSTEM
METER IS ON
CLEARANCE TAG GIVEN
02/06/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE WARNING LABEL ON FRONT OF HEATER OR SEE PAGE 41
2) PROVIDE THE MINIMUM 36" OF CLEARANCE FROM COMBUSTIBLE MATERIALS TO TOP OF HEATER
3) IS GAS PIPING BONDED TO ALL METALIC PIPING SYSTEM ? IF NOT BOND TO PANEL
01/25/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WH INSTALLATION DOES NOT MEET REQUIRED CLEARANCE FROM COMBUSTIBLES.
PROVIDE INSTALLATION INSTRUCTIONS
PROVIDE ELECTRICAL BONDING
FLEX NOT RATED FOR 190,000 BTU
PRESSURE TEST OK
01/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. IVR SYSTEM DOWN UNABLE TO ACCESS MESSAGE
2. NOBODY HOME

REINSPECTED
PLEASE DO NOT MAX OUT PRESSURE GAUGE
TEST IN THE MID-RANGE OF THE GAUGE
REMOVE 90 DEG. ELL AT BOTTOM OF T&P RELIEF DRAIN
PROVIDE ACCESS TO ROOF
APPROVED VALVE AT STOVE AGA CSA
WATER HEATER AND FURNACE REQUIRE SEDIMENT TRAPS

WATER LINE REPIPE REQUIRES A PERMIT
PROVIDE LISTING FOR GLK PLASTIC
PROVIDE HAMMER ARRESTORS AT LAUNDRY.