Permit: T07PL00100

Parcel: 113010720


Addresses:

3819 N VINE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/26/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/23/2007 PLUMBING - FINAL Not ready for Inspection 1. INSTALL WH, VENTING, SEDIMENT TRAPS, AGA VALVES
2. PROVIDE AN APPROVED INDIRECT RECEPTOR W/TRAP
FOR T&P DRAIN.
3. SECURE PIPING AT WH AND AT METER.
4. EXTEND B VENTS TO 3' ABOVE COOLER
5. PROVIDE ELECTRICAL BONDING.
01/23/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES FROM PREVIOUS INSP.
SECURE WH AND FURNACE VENTS W/3 GALV SHEETMETAL SCREWS IN EACH JOINT. NO TAPE AT TRANSITION TO B VENT
EXTEND B VENT TO 3 FEET ABOVE FORCED AIR INLET
DRAIN TEMPERATURE PRESSURE RELIEF VALVE INDIRECTLY TO AN APPROVED RECEPTOR OR PROVIDE A PETITION OF APPEAL.
SECURE PIPING AT WH & FURNACE
INSTALL SEDIMENT TRAPS.