Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK FOR GAS UCC LEFT AT METER SW GAS 889-1888 |
|
| 01/17/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. I CALLED 292-6457 NO ANSWER 2. I KNOCKED ON THE DOOR, NO ANSWER |
|
| 01/16/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HORIZONTAL SECTION OF U.G GAS TO BE A MINIMUM OF 30" 2. PVC NOT APPROVED FOR T&P RELIEF DRAIN DRAIN TO EXTEND TO OUTSIDE BLDG. 3. WATER HEATER AND FURNACE REQUIRE SEDIMENT TRAPS 4. REQUIRE BOND BETWEEN GAS PIPE AND WATER PIPE 5. GAS FLEX MAY NOT PASS THRU WALL OR PARTITION 6. WATER PIPE REPAIRED U.G COPPER MAY NOT CONNECT TO IRON PIPE. 7. WATER HEATER/FURNACE VENT WITHIN 10' OF AIR INTAKE TO BE EXTENDED. |