Permit: T07PL00085

Parcel: 106070990


Addresses:

3341 N EL TOVAR AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/19/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR GAS
UCC LEFT AT METER
SW GAS 889-1888
01/17/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. I CALLED 292-6457 NO ANSWER
2. I KNOCKED ON THE DOOR, NO ANSWER
01/16/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HORIZONTAL SECTION OF U.G GAS TO BE A MINIMUM OF 30"
2. PVC NOT APPROVED FOR T&P RELIEF DRAIN
DRAIN TO EXTEND TO OUTSIDE BLDG.
3. WATER HEATER AND FURNACE REQUIRE SEDIMENT TRAPS
4. REQUIRE BOND BETWEEN GAS PIPE AND WATER PIPE
5. GAS FLEX MAY NOT PASS THRU WALL OR PARTITION
6. WATER PIPE REPAIRED U.G COPPER MAY NOT CONNECT TO IRON PIPE.
7. WATER HEATER/FURNACE VENT WITHIN 10' OF AIR INTAKE TO BE EXTENDED.