Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PET. OF APPEAL #004 07 - OK 2. TOOL MARKS FROM PIPE THREADER ON SCOTCH KOTE BELOW GRADE. SEE PREVIOUS INSP NOTES (#1, 4, 7) 3. BOND TO NON-COATED PIPING 4. CAP DRAIN ON WH DRAIN PAN 5. FURNACE VENT SHALL ALSO TERMINATE ABV COOLER |
|
| 01/17/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PRESSURE TEST OK 1. SOME TOOL MARKS ON PIPING OFFSETS JUST INSIDE FENCE PRIME THEN WRAP TOOL MARKS. 2. PROVIDE PETITION OF APPEAL FOR WH T&P TERMINATION 3. PROVIDE EXTERIOR PRESSURE RELIEF VALVE 4. PROVIDE PROOF OF INSPECTION FOR NEW FURNACE. 5. PROVIDE CORRECT SIZE NEW FLEX FOR 125,000 BTU FURNACE. 6. INSTALL SEDIMENT TRAP 7. TERMINATE VENT TWO FEET ABOVE COOLER. |