Permit: T07PL00069

Parcel: 110043780


Addresses:

3343 N SAGEWOOD DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/23/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10:27 COULD NOT RETRIEVE MESSAGE
NO ACCESS - GATES LOCKED
01/19/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
YOU HAVE LONG SECTIONS OF TUBING IN THE CEILING THAT ARE NOT SECURED, YOU MUST INSTALL PEX PER THE CODE REQUIREMENTS.
01/18/2007 PLUMBING - FINAL Denied IVRS - Inspection :
1. SUPPORT AND SECURE HORIZONTAL PIPING AT 32"
2. KEEP PIPING AWAY FROM LIGHTS.
3. CORRECT KINK ON COPPER AT HALL LAV.
4. ISOLATE PEX FROM MASONRY AT MASTER SHOWER.
5. CAP OR CAULK ABANDON STUB OUTS MASTER LAVS.
6. INSTALL HAMMER ARRESTORS AT WASHER BOX.