Permit: T07PL00016

Parcel: 116161980


Addresses:

809 N CONTZEN AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/08/2007 PLUMBING - FINAL Not ready for Inspection POST ADDRESS
TERMINATE TYPE B VENT 1' ABOVE ROOF
PROVIDE BONDING
01/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. WATER HEATER INSTALLED W/O PERMIT
A. SEDIMENT TRAP
B. APPROVED T&P RELIEF DRAIN
C. EXTEND VENT
D. FLEX MAY NOT PASS THRU PARTITION
2. SEAL EXTERIOR PENETRATION