Permit: T07PL00014

Parcel: 11106075B

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Permit Number - T07PL00014

Inspection Description - PLUMBING - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
02/07/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 15 PSI TEST FROM METER TO WATER HEATER STOVE AND WALL HEATER ON MOSTLY EXISTING PIPING OK
2) GAS CARD AT METER
3) SHALL GO TO 201 N. STONE PAY REFEE AND CALL IN ALL INSPECTIONS ON THIS PERMIT 03052, 03065, 03090 TO FINAL THIS PERMIT. NOTE: IF REFEE NOT PAID ANY FUTURE PERMITS ON THIS SITE WOULD BE HELD UP
4) SHALL PROVIDE COVER FOR WALL HEATER TO AVOID BURN HAZARD
01/26/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SHALL PAY REFEE, NO CHANGE FROM PAST INSPECTION
THIS IS NOT A GAS RECONNECT, NEW PIPING HAS BEEN ADDED. TEST SHALL BE HOLDING IN PLACE AT TIME OF INSPECTION. ALL PIPING SHALL BE MINIMUM 3 1/2" ABOVE GRADE WHEN ABOVE GRADE. ALL PIPING SHALL BE SUPPORTED CORRECTLY AND SECURED CORRECTLY. CALL IN BOTH PERMITS AS REQUESTED. READ ALL NOTES FROM ALL PAST INSPECTIONS LEFT AT SITE. PLEASE HAVE A PLUMBER ON SITE TO BE INFORMED OF 2003 UPC REQUIREMENTS. NO GAS CLEARANCE SHALL BE ISSUED UNTIL ALL INSPECTIONS ARE APPROVED AND REFEE PAID.
01/25/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DANA 888-2579

1. TEST SHALL HOLD WITH NO PRESSURE LOSS FOR 10 MINUTES.
2. SUPPORT GAS PIPING CORRECTLY AT KITCHEN LOCATION & METER LOCATION.
3. SECURE WEATHERPROOF ENCLOSURE TO WATER HEATER PAD.
4. PROVIDE BONDING OF BUILDING GAS PIPING PER 1/9/07 INSPECTION.
5. CALL IN PERMIT #T07PL00014 WITH PERMIT #T07PL00070
AND FILL WATER HEATER PIPING & WATER HEATER WITH WATER.