Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PETITION OF APPEAL #2007-244 ON SITE 1. SHALL PROVIDE 1" AIR GAP FOR T&P DRAIN AND TOP OF PAN AT WATER HEATER. 2. SHALL TERMINATE 125# PRESSURE RELIEF IN DOWNWARD ANGLE WITH NIPPLE WITH NO THREADS ON DISCHARGE END. 3. PERMANENT CAP AND OR REMOVE OLD GAS PIPING. 1. SECURE GAS PIPING AT STOVE DROP AND ON ROOF AT CORRECT INTERVALS. 2. PROVIDE RATED FLEX TO MEET 110,000 BTU REQUIREMENT OF ROOFTOP UNIT THAT IS LONG ENOUGH TO REACH UNIT. |