Permit: T07OT02779

Parcel: 11011181B


Addresses:

5099 E GRANT RD

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
04/29/2008 SIGN SHOP Approved IVRS - Inspection :*
04/25/2008 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND
MAX 6' INTERVALS
2. MC TO FIT INTO CONNECTORS FULLY
3. FASTEN TO STRUCTURE OR USE ANCHORS - NOT SCREWS INTO DRYWALL
4. LOW VOLTAGE WIRING TO BE RAN IN A NEAT AND WORKMANLIKE MANNER
5. REMOVE DEMO'D/UNUSED WIRING
6. USE PROPER DEVICE TO GROUND ENCLOSURES SUCH AS GROUND LUGS
04/23/2008 SIGN SHOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALLATION IS A MESS
GO THROUGH INSTALLATION AND MAKE SURE ALL IS PER CODE AND DONE IN A NEAT AND WORKMANLIKE MANNER
NO INSPECTION AT THIS TIME.