Permit: T07OT02681

Parcel: 12106286A


Addresses:

5872 E PIMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/13/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
02/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROPERLY SOLDER ALL FITTINGS
01/30/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
SOLDER ALL COPPER FITTINGS ON CONDENSATE DRAIN
01/23/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/30/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SECURE CONDUITS ON ROOF
SECURE GAS LINES ON ROOF
REPAIR BROKEN CONDUITS
PROVIDE CONDENSATE TRAPS ON 2ND FLOOR UNITS
AC UNITS NOT PROPERLY SUPPORTED
ELEC. DISCONNECT MOUNTED TO SERVICE PANEL
1 DISCONNECT NO WORKING CLEARANCE