Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SPACE IS OCCUPIED BEFORE APPROVAL CALL FOR INSPECTION WHEN ORIGINAL INSPECTOR IS BACK IN OFFICE 2/26/08 GINGER 661-5335 RIMLINE LARRY 891-6769 |
|
| 01/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE 2. NEED DISCONNECTING MEANS FOR WATER HEATER 3. WHERE IS GROUNDING EQUIPMENT CONDUCTOR FOR WATER HEATER 4. ARE CONDUCTORS UNGROUNDED OR GROUNDED? 5. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 6. RECEPTACLE COVERS TO BE WEATHERPROOF - 406.8 7. PROPERLY GROUND BOXES 8. BOND SUB-PANEL 9. FINISH PREVIOUS ITEMS 10. PLEASE PROVIDE ACCESS TO INSIDE LIGHTS AND ROOF 11. CANNOT USE GROUNDED CONDUCTOR FOR GROUNDING |
|
| 11/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF: 1. MAINTANANCE RECEPTACLE TO BE GFCI & WEATHERPROOF 210.63, 408.6 2. SUPPORT CONDUITS TO LIGHTING & TIGHTEN LOOSE FITTINGS 3. BROKEN LIGHT FIXTURE BUILDING: 1. MISSING COVER PLATES 2. FILL UNUSED OPENING IN BOXES 3. USE CORRECT COLORS FOR CONDUCTORS 4. GROUND METAL BOXES 5. SECURE CONDUIT FITTING TO SUB-PANEL 6. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 7. CLEAN OUT FOREIGN MATERIAL FROM SUB-PANEL 8. LABEL CIRCUIT DIRECTORY PER 408.6 9. USE CORRECT FIXTURE FOR BOX 10. FOUNTAIN TO BE GFCI PROTECTED 11. CLEAN EXCESS PAINT FROM DEVICES 12. EXPOSED CONDUCTORS & CABLES 13. SEAL ENTRANCE AT SERVICE 14. LABEL METERS 15. HAVE A QUALIFIED ELECTRICIAN REPAIR WORK STILL NUMEROUS VIOLATIONS |