Permit: T07OT02681

Parcel: 12106286A


Addresses:

5872 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SPACE IS OCCUPIED BEFORE APPROVAL
CALL FOR INSPECTION WHEN ORIGINAL INSPECTOR IS BACK
IN OFFICE 2/26/08

GINGER 661-5335
RIMLINE
LARRY 891-6769
01/30/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE
2. NEED DISCONNECTING MEANS FOR WATER HEATER
3. WHERE IS GROUNDING EQUIPMENT CONDUCTOR FOR WATER HEATER
4. ARE CONDUCTORS UNGROUNDED OR GROUNDED?
5. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
6. RECEPTACLE COVERS TO BE WEATHERPROOF - 406.8
7. PROPERLY GROUND BOXES
8. BOND SUB-PANEL
9. FINISH PREVIOUS ITEMS
10. PLEASE PROVIDE ACCESS TO INSIDE LIGHTS AND ROOF
11. CANNOT USE GROUNDED CONDUCTOR FOR GROUNDING
11/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ROOF:
1. MAINTANANCE RECEPTACLE TO BE GFCI & WEATHERPROOF
210.63, 408.6
2. SUPPORT CONDUITS TO LIGHTING & TIGHTEN LOOSE FITTINGS
3. BROKEN LIGHT FIXTURE

BUILDING:
1. MISSING COVER PLATES
2. FILL UNUSED OPENING IN BOXES
3. USE CORRECT COLORS FOR CONDUCTORS
4. GROUND METAL BOXES
5. SECURE CONDUIT FITTING TO SUB-PANEL
6. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
7. CLEAN OUT FOREIGN MATERIAL FROM SUB-PANEL
8. LABEL CIRCUIT DIRECTORY PER 408.6
9. USE CORRECT FIXTURE FOR BOX
10. FOUNTAIN TO BE GFCI PROTECTED
11. CLEAN EXCESS PAINT FROM DEVICES
12. EXPOSED CONDUCTORS & CABLES
13. SEAL ENTRANCE AT SERVICE
14. LABEL METERS
15. HAVE A QUALIFIED ELECTRICIAN REPAIR WORK
STILL NUMEROUS VIOLATIONS