Permit: T07OT02641

Parcel: 11445262J

Inspection Status: Denied

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
08/07/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NO WORK PROGRESS
02/13/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. A MARKING LABEL IS NEEDED
2. USE APPROVED NIPPLE OR PASS THROUGH BETWEEN RACEWAYS
3. BOND RACEWAY
4. MAINTAIN 1 1/2" CLEARANCE TO HIGH VOLTAGE TERMINALS
5. CLEAN FOREIGN MATERIAL FROM RACEWAY
6. DO NOT ENERGIZE UNTIL FINALED BY ELECTRICAL INSPECTOR
01/14/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CHECK ON SITE