Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2008 | FIRE - FINAL | Denied | 1.) Automatic sprinkler system is required. 2.) Requires alarm system to be installed. 3.) Emergency lighting. 4.) Exit signs 5.) Remove double-keyed locks from kiln/ ceramic room exit. |
|
| 03/04/2008 | FIRE - FINAL | Denied | I-4 is required to have a sprinkler and alarm system installed. A couple of other smaller items need addressing in addition to the ADA requirements set forth by DSD ( Lee Ray Hanley). Denied. |