Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT02375
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
11/02/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* | |
11/01/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN GTO CLEARANCES 2. PROVIDE GROUND FAULT PATH FOR METAL FLEX 3. SUPPORT MC CABLE 4. LIGHT NOT AFTER TIME CLOCK 5. SWITCH TO BE CAPABLE OF BEING LOCKED OUT |
|
10/25/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ISOLATE POWER TO SWITCH 2. TERMINAL END ONLY ALLOW ONE CONDUCTOR PER CRIMP 3. MAINTAIN GTO CLEARANCES |