Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T07OT02218
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SPLICES NOT LISTED FOR WET LOCATIONS 2. PRIMARY CONDUCTORS TO BE ISOLATED TO SWITCH 3. USE APPROVED FITTINGS WITH SEAL TIGHT 4. TIGHTEN LOOSE FITTINGS 5. MAINTAIN BOND PATH |