Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2008 | FIRE - FINAL | Approved | ||
| 03/31/2008 | FIRE - FINAL | Denied | Not Approved, 3/31/08. 1.) Provide sign over main door reading, "THIS DOOR TO REMAIN UNLOCED WHILE BUILDING IS OCCUPIED". 2.) Opening in ceiling next to fan, main eating area. 3.) Missing cover plate, kitchen area. 4.) Extension cords being used as permanent wiring for coolers shall be removed. 5.) Clean the grease build-up on all sprinkler heads. 6.) Remove security bar and keyed- lock from back door, provide a thumb-turn lock. 7.) Dry chemical hood system shall be serviced or replace with a UL/300 system. |