Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT02195
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2008 | SIGN SHOP | Approved | IVRS - Inspection :* | |
01/11/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
12/13/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK FREEWAY SIGN OK FASTLANE LETTERS OK EAST CAR WASH LETTERS 1. FINISH PREVIOUS ITEMS 2. SERVICE TRANSFORMER ENCLOSURE EAST CARWASH |
|
11/13/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A SERVICE LIGHT PER 210.70 IS NEEDED 2) TIGHTEN HIGH VOLTAGE TERMINATIONS AND MAINTAIN CLEARANCES BOTH NEON 3) ISOLATE POWER TO SIGN MONUMENTS 4) NEED ACCESS TO FREEWAY SIGN AND FAST LANE 5) INSTALL EAST CARWASH 6) TIGHTEN LOOSE FITTINGS-NEON |
|
11/08/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* | |
10/24/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK NOBLE PIZZA X 2, CHEVRON X2 & LOGO X2 ON CANOPY PUMP SIGN X6 1. NO POWER TO CANOPY LED |