Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | FIRE - FINAL | Approved | All corrections made. Approved for C of O. | |
| 02/01/2008 | FIRE - FINAL | Not ready for Inspection | STILL NEED ADDRESS NUMBERS | |
| 01/14/2008 | FIRE - FINAL | Not ready for Inspection | INSPECTED STORAGE ROOM #4 NO PROBLEMS. | |
| 11/26/2007 | FIRE - FINAL | Denied | INSPECTION DONE ON STORAGE ROOM #3, NEED TO REPAIR WIRNG TO COOLER CAN NOT USE EXTENSION CORD FOR PERMENT WIRING. SHALL WIRE COOLER PER NEC CODES. NEED TO REPAIR OUTLET BOX NEXT TO MAIN BREAKER BOX. STILL NEED TO INSPECT STORAGE ROOM #4 |
|
| 11/23/2007 | FIRE - FINAL | Denied | 1.) IFC 505.1 ADDRESS NUMBERS SHALL BE POST UP ON BUILDING A BIG TRUCK WAS BLOCKING NUMBERS THAT ARE POSTED LOWER BY FRONT DOOR. NUMBERS NEED TO BE 15" IN SIZE. (PAPERWORK FOR PROPER INSTALATION WAS GIVEN) 2. GATE TO STORAGE AREA NEEDS TO OPERATE ALL THE WAY BOTH GATES NEED TO OPEN SO THERE IS A 20' CLEARANCE. 3. NEED TO ADD A FIRE DEPT KEY SYSTEM OR USE A SMALLER CHAIN TO LOCK GATES. CHAIN IS TO BIG FD CAN NOT CUT CHAIN THAT BIG, FD CAN NOT CUT CASE HARDED PAD LOCKS. 4.) IN STORAGE UNIT #2 AND #5 NEED TO REPAIR OR REPLACE BREAKER BOX MISSING COVER PANEL, IN #2 NEED TO REPLACE BROKEN OUTLET UNDER BREAKER BOX. 5.) NEED TO INSPECT #3 AND #4 WILL BE BACK AT 10:00AM 11/26/07. |