Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 12/26/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MARKING LABELS STILL NOT ON 2) TIGHTEN LOOSE FITTINGS 3) FILL UNUSED OPENINGS IN BOXES 4) USE APPROVED EXTENDER BOXES 5) CONNECT ALL GROUNDS 6) BOND POWER SUPPLY ENCLOSURE 7) SWITCH TO BE EXTERNALLY AND OR CAPEABLE OF BEING LOCKED OPEN |
|
| 12/21/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 11/27/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1) NEED MARKING LABELS 2) SWITCH TO BE EXTERNALY OPERABLE 600.6 3) DO NOT ENERGIZE UNTIL FINALED BY ELECTRIC INSPECTOR |