Permit: T07OT02042

Parcel: 13314143D


Addresses:

1340 N WILMOT RD

Inspection Status: Denied

Inspection History: CERTIFICATE OF OCCUPANCY

Date Description Inspector Results Comments
11/26/2007 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
#2,3,6 FROM 9/12/07 AND
A. ALL INDIRECT WASTE TO TERMINATE 1" ABOVE FLOOR DRAINS
B. BACKFLOW PROTECTION REQUIRED AT ICE MACHINE
C. PERMANENT CAP REQUIRED ON UNUSED GAS TAPS @ HOOD
D. CAULK TOILETS & SINK
E. COVER OPENINGS IN ELEC. PANEL
F. EMERGENCY EGRESS LIGHTING NOT WORKING
09/13/2007 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/12/2007 CERTIFICATE OF OCCUPANCY Not ready for Inspection IVRS - Inspection :*
1. PROVIDE FIRE C OF O APPROVAL
2. CONDENSATE DRAINS? ON NORTH SIDE BY GAS METER MUST BE PROPERLY TERMINATED
3. PRESSURE VACUUM BREAKER REQUIRED AT EXTERIOR MOP SINK (NO VALVES ALLOWED DOWNSTREAM OF AVB)
4. ALL EXTERIOR LIGHTING & WIRING MUST MEET CODE AND BE IN GOOD REPAIR (TOP OF ROOF ALSO)
5. READILY ACCESSIBLE DISCONNECT REQUIRED AT SERVICE ENTRANCE
6. ABS VENT STACK AND CLEANOUT WITH AIV (STUDOR VENT) BY EXTERIOR MOP SINK MUST MEET CODE
7. PROVIDE ACCESS INTO BUILDING

THIS MAY NOT BE A COMPLETE LIST