Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2007 | FIRE - FINAL | Partial Approval | TEMP C OF O ONLY 1. Need flammable cabinet for flammable and combustibles totaling over 10 gals. 2. Repair all exit signs, not working. 3. Fix exhaust vent piping to hot water heater in back yard. 4. Fix exhaust vent to room heater in back room. 5. Remove padlock off of exit door in hallway. 6. Remove double cylinder lock dead bolt lock from southwest exit door need thumb style lock. 7. Remove slide bolt locks from exit doors southeast room and northeast room. 8. Need fire extinguishers every 75 feet. 9. No storage around vent piping in office area. |