Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T07OT01964
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | ELECTRIC - PROGRESS | Approved | OK PER NOTES FROM PREVIOUS INSP. | |
09/07/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* CHECK EXISTING ELECTRIC FOR LIFE/SAFETY ISSUES 1. THIS STRUCTURE HAS ELECTRICAL WORK BEING DONE UNDER SEPARATE PERMIT THAT HAS NOT BEEN FINALED YET 2. HAVE OPEN WIRING THROUGHOUT ON INTERIOR AND EXTERIOR OF STRUCTURE, IE MISSING FIXTURES, MISSING COVERS, OPEN J-BOXES, ETC. 3. BATHROOM RECEPTACLES NOT GFI PROTECTED 4. HAVE RECEPTACLES THAT ARE LOOSE/SET BACK IN WALL 5. HAVE SEVERAL LIGHT FIXTURES MISSING BULBS/COVERS 6. EXISTING PANELS HAVE OPEN BREAKER SPACES, DIRECTORIES NOT MARKED 7. HAVE OPEN ENERGIZED ROMEX UPSTAIRS 8. STAIR 3-WAY SWITCH NOT WORKING 9. EMERGENCY LIGHTING NOT WORKING, OPEN ENERGIZED SPLICES THROUGHOUT - STRUCTURE NOT SAFE TO OCCUPY RECOMMEND ELECTRICAL CONTRACTOR GO THROUGH AND MAKE SAFE. INSPECTION TIME 45 MIN. |