Permit: T07OT01810

Parcel: 11706187D


Addresses:

278 E CONGRESS ST


Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Permit Number - T07OT01810

Inspection Description - CERTIFICATE OF OCCUPANCY

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2007 CERTIFICATE OF OCCUPANCY Approved PER LEERAY AND SIGNED C OF O IN SIRE
08/13/2007 CERTIFICATE OF OCCUPANCY Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 12" ADDRESS DISPLAY REQUIRED PER PIMA COUNTY ZONING ORDINANCE
2. 1" CLEARANCE REQUIRED AROUND EXHAUST VENT @ HEATER
3. USE LISTED AGA OR CSA GAS VALVE @ SUSPENDED HEATER
4. WATER HEATER TO BE ON DEDICATED CIRCUIT OR REMOVED
5. SINK IN STORAGE ROOM MAY NOT BE WET VENTED @ WATER CLOSET. INSTALL PER UPC OR DELETE.