Permit: T07OT01672

Parcel: 12510003G


Addresses:

3485 E BROADWAY BL

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
11/16/2007 SIGN SHOP Approved IVRS - Inspection :*
OK SIGNS
11/15/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
FINISH ITEMS 1 & 6
OK NORTH ROSS & BLADE SIGN
11/13/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT M/C CABLE PER CODE 12" + 6'
2) FILL UNUSED OPENING IN TRANSFORMER ENCLOSURE
3) BOND ENCLOSURER
4) IS SWITCH LOCKABLE PER 600.6
5) BOX COVER NOT ACCESSIBLE
6) INSTALL 2 RODS LOGO'S NORTH AND WEST INTERIOR WALL
10/18/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
DO NOT CALL IN BEFORE READY

YOU WILL ALSO NEED TO PAY A REINSPECTION FEE -
BEFORE FINAL APPROVAL
10/12/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
10/11/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
FINISH INSTALL
10/10/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
OK FRONT SOFFIT FOR POWER SUPPLIES & WIRING METHODS
OK FRONT SIGN
09/19/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
1) OK LED COMPONENTS
09/06/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PLEASE VERIFY COMPONENTS FOR LISTING IN SAM MANUAL
08/31/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELLED
08/21/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
1. MAINTAIN GTO CLEARANCES
2. SWITCH TO BE EXTERNALLY OPERABLE 600.6
3. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR