Permit: T07OT01549

Parcel: 131044020


Addresses:

4831 E 29TH ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
10/22/2007 FIRE - FINAL Approved
09/26/2007 FIRE - FINAL Denied Extension cords not allowed:
1. Office 2. Shop area behine water cooler
3. Waiting room 4. Shop area - light on ceciling
Repair or replace outlet in 2nd office, wiring hanging out.
Need cover plates on all outlets and switches
1. 2nd office 2. Storage area behine shirts
3. 1st shop area 4. 2nd storage area
Need conduit on wirng below 7 feet height, shop area where tool boxes are.