Permit: T07OT01549

Parcel: 131044020


Addresses:

4831 E 29TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BATHROOM RECEPTACLE TO BE GFI PROTECTED
2. INSTALL K.O SEALS WHERE MISSING
3. INSTALL JUNCTION BOX COVERS
4. ALL WIRING TO BE CONNECTED TO JUNCTION BOXES WITH CONNECTORS
5. GROUND ALL JUNCTION BOXES
6. HAVE OPEN SPLICE IN SHOP AREA TO NON-APPROVED WIRING METHOD. NEEDS TO BE REMOVED
7. PROVIDE LADDER FOR ROOF ACCESS
8. COMPLETE ITEMS 1,4,6,8,11 FROM PREVIOUS INSPECTION
9. HAVE QUALIFIED ELECTRICIAN/CONTRACTOR GO THROUGH ENTIRE BUILDING & MAKE REPAIRS AS REQUIRED. THIS IS NOT A COMPLETE LIST.
09/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT RUN EXTENSION CORD THROUGH WALL. CANNOT BE USED AS PERMANENT WIRING.
2. INSTALL MISSING DEVICE PLATES
3. INSTALL MISSING RECEPTACLES
4. MISSING GROUND CONNECTION AT RECEPTACLES
5. REPLACE DAMAGED CORDS
6. REMOVE EXTENSION CORDS & PROVIDE PERMANENT WIRING/OUTLETS
7. HAVE REVERSE POLARITY ON RECEPTACLES
8. RECEPTACLES TO BE MIN. 18" ABOVE FLOOR IN SHOP AREA
9. AIR COMPRESSOR NOT WIRED PER CODE
10. NUMEROUS CODE VIOLATIONS HAVE QUALIFIED ELECTRICIAN MAKE CORRECTIONS/REPAIRS AND GO THROUGH ENTIRE BUILDING
11. VERIFY PERMIT FOR NEW AUTO LIFT