07/09/2007 SIGN SHOP Approved IVRS - Inspection :*
07/06/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
BORDER NEON:
1. INSTALL FITTINGS TO BOND PLATE AS PER CODE -- 110.3
2. USE APPROVED FITTINGS FOR M/C CABLE -- 110.3

SIGN:
1. A WALKWAY IS NEEDED -- 600.21
2. A SERVICE LIGHT IS NEEDED -- 210.70
3. GROUND CONDUCTOR NOT ALLOWED IN GTO RACEWAY
4. SWITCH TO BE AS PER 600.6
5. BONDING OF LETTERS TO BE PER ARTICLE 250.8
6. MARKING LABEL AS PER 600.4 IS NEEDED