Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2008 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 02/28/2008 | SIGN SHOP | Partial Approval | IVRS - Inspection :* WAITING ON REVISED PLANS |
|
| 02/27/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NORTH SIGN 1. BOND BUSHINGS PER 250.97 2. TIGHTEN LOOSE FITTINGS 3. REVISE PLANS FOR 480V EQUIPMENT 4. PROVIDE OVER CURRENT PROTECTION PER 240.21 5. HANDY BOX OVERFILLED 410.16 6. SUPPORT M/C CABLE |