Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07OT01441

Parcel: 12511251A


Addresses:

615 N ALVERNON WY


Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T07OT01441

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
07/24/2008 SIGN SHOP Approved IVRS - Inspection :*
06/24/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SWITCH TO BE ISOLATED ON PRIMARY SIDE CONDUCTORS
2. PROPERLY GROUND JUNCTION BOXES 3/4 OF A TURN
02/08/2008 SIGN SHOP Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NO WORK PROGRESS
PLEASE PAY REFEE BEFORE NEXT INSPECTION
02/07/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELED
02/06/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELED
01/31/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SWITCH TO BE AS PER 600.6 - EXTERNALLY OPERABLE
12/05/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1. A DISCONNECTING MEANS IS NEEDED 600.6
2. A MARKING LABEL IS NEEDED 600.4
3. PLEASE VERIFY JUNCTION BOX GROUNDING