Permit: T07OT01389
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2008 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 03/19/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK TRENCH #5 PREVIOUS INSPECTION |
|
| 03/17/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 01/07/2008 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. PVC CONDUIT UNDER PAVEMENT TO BE AS PER 300.5 24" 2. FINISH PREVIOUS ITEMS 5 & 7 |
|
| 10/23/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLUMBING 90 DEG. NOT ALLOWED FOR ELECTRICAL 2. SECURELY ATTACH CONDUIT 3. SUPPORT JUNCTION BOX AND PROTECT FROM PHYSICAL DAMAGE 4. USE PROPER METHODS FOR PVC CONNECTORS 5. VERIFY LED FOR USE IN SAM MANUAL 6. GROUND JUNCTION BOXES 7. PLEASE VERIFY INSPECTIONS FOR POWER ACROSS CAR LOT UNDER ASPHALT 8. JUNCTION BOX TO BE ACCESSIBLE |