Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OLD WIRE (ROMEX) FROM PANEL & SEAL OPENING NEC 110.12 2. SEAL OPEN KNOCKOUT IN PANEL - NEC 110.12 3. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL NEC 110.3 4. PANEL DIRECTORY NEEDED - NEC 408.4 |