Inspection Status: Denied
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS ITEMS #2 & #3 |
|
| 08/29/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY ALL UNGROUNDED CONDUCTOR - 277V 2. PLEASE VERIFY CIRCUIT PER 600.5 3. SPLICES TO BE FOR WET LOCATION |
|
| 06/20/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK SHOP 1. CHECK POWER ON SITE 2. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR 3. CHECK MARKING LABEL ON SITE |