Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | CERTIFICATE OF OCCUPANCY | Approved | FIRE APPROVED BY L THOMAS 6/25/07 | |
| 06/22/2007 | CERTIFICATE OF OCCUPANCY | Not ready for Inspection | IVRS - Inspection :* NEED FIRE APPROVAL - OTHER CORRECTIONS COMPLETE |
|
| 06/06/2007 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ACCESSIBLE PARKING SPACE MUST BE LOCATED ON FLAT AREA. 2. EXTERIOR HOSE BIBBS MUST HAVE ANTI-SIPHON DEVICES 3. IRRIGATION LINE REQUIRES BACKFLOW PROTECTION 4. EMERGENCY EGRESS LIGHTING REQUIRED 5. CAULK TOILET AT FLOOR 6. CAULK LAVATORY AT WALL 7. WALLS WITHIN 2' OF TOILET TO BE HARD, IMPERMEABLE SURFACE (4' HIGH) 8. DOOR HARDWARE FROM RESTROOM TO UNLOCK WHEN TURNED FROM INSIDE 9. ACCESSIBLE SIGNAGE REQUIRE FOR UNISEX 10. LEVER HANDLE HARDWARE REQUIRED ON ACCESSIBLE ROUTE. |