Permit: T07OT01094

Parcel: 10408093B


Addresses:

625 W AUTO MALL DR

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
09/04/2007 SIGN SHOP Approved IVRS - Inspection :*
08/24/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY GROUNDING CONDUCTORS 250.119
2. CANNOT STACK LUGS
3. CLEAN SURFACE BENEATH GROUND BAR 250.12
4. GROUND JUNCTION BOX
08/23/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
08/14/2007 SIGN SHOP Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
07/31/2007 SIGN SHOP Partial Approval IVRS - Inspection :$
07/31/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN WORKING CLEARANCES IN FRONT OF PANEL
2. VERIFY GROUNDING ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEM
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
4. FILL UNUSED OPENINGS IN DEAD FRONT COVER
5. LABEL BREAKERS
6. SEPARATE GROUNDS & NEUTRALS AT PANEL
7. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.
07/30/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
07/26/2007 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELLED
07/17/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
1. ALL METALLIC PARTS TO BE GROUNDED 600.7
AND AS PER PLANS.
2. CHECK POWER ON SITE
3. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.