Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2010 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* | |
| 07/05/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL STUDS TO HAVE MARKING LABELS 600.4 -- FILL OUT STARBUCKS LABEL 2. WALKWAY IS NEEDED AS PER 600.21 3. SERVICE LIGHTS ARE NEEDED -- 210.70 4. CORD NOT ALLOWED FOR SIGN 400.7 & 8 UL 48 16.3.13 & 171 5. DO NOT INSTALL CITY STICKERS UNTIL CITY INSPECTOR PASSES SIGN 6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
| 06/29/2007 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* CANCELLED |