Permit: T07OT00963

Parcel: 12801005H

Inspection Status: Denied

Inspection History: SIGN SHOP

Permit Number - T07OT00963

Inspection Description - SIGN SHOP

Inspection Status - Denied

Date Description Inspector Results Comments
02/06/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO PLANS ON SITE WITH THE PERMIT
2. JUNCTION BOXES NEED TO BE ACCESSIBLE
3. FINISH PREVIOUS ITEMS 3
4. LABEL CIRCUIT FOR SIGN
5. CANNOT USE SHEETMETAL THREAD SCREW FOR GROUNDING - 250.8
01/25/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELED
01/23/2008 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
CANCELLED
12/07/2007 SIGN SHOP Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
09/05/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PLEASE HAVE SIGN CONTRACTOR ON SITE TO OPEN AND ACCESS SIGN.
2. A MARKING LABEL IS NEEDED - 600.4
3. SWITCHING TO BE AS PER 600.6
4. PLEASE VERIFY SIGN CIRCUIT IS AS PER 600.5
5. ARE LED SIGNS BONDED PER 600.7
6. IS LED DRIVER LISTED IN S.A.M MANUAL