Inspection History Details
Inspection Status: Denied
Inspection History: SIGN SHOP
Permit Number - T07OT00963
Inspection Description - SIGN SHOP
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO PLANS ON SITE WITH THE PERMIT 2. JUNCTION BOXES NEED TO BE ACCESSIBLE 3. FINISH PREVIOUS ITEMS 3 4. LABEL CIRCUIT FOR SIGN 5. CANNOT USE SHEETMETAL THREAD SCREW FOR GROUNDING - 250.8 |
|
01/25/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/23/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
12/07/2007 | SIGN SHOP | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS |
|
09/05/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PLEASE HAVE SIGN CONTRACTOR ON SITE TO OPEN AND ACCESS SIGN. 2. A MARKING LABEL IS NEEDED - 600.4 3. SWITCHING TO BE AS PER 600.6 4. PLEASE VERIFY SIGN CIRCUIT IS AS PER 600.5 5. ARE LED SIGNS BONDED PER 600.7 6. IS LED DRIVER LISTED IN S.A.M MANUAL |