Permit: T07OT00929

Parcel: 12108066A


Addresses:

6161 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: CERTIFICATE OF OCCUPANCY

Date Description Inspector Results Comments
06/01/2007 CERTIFICATE OF OCCUPANCY Approved PER SIGNATURE ON CARD
05/31/2007 CERTIFICATE OF OCCUPANCY Cancelled IVRS - RI canceled
05/09/2007 CERTIFICATE OF OCCUPANCY Denied 1. ACCESSIBLE PATH REQUIRES LEVER HANDLE "NO KNOWLEDGE" HARDWARE
2. PROVIDE ACCESSIBLE PATH TO ALL COMMON AREAS
3. PROVIDE LEVEL LANDINGS AT ENTRANCES AND EXITS
4. REMOVE CHAINS/CLASPS OR OTHER SUCH LOCKING DEVICES ON EXITS
5. INSULATE DRAIN IN ACCESSIBLE LAVATORIES
6. FLUSH HANDLE TO BE ON WIDE SIDE OF ROOM IN ACCESSIBLE TOILET
7. SEAL (CAULK) ALL SINKS @ COUNTER, TOILETS AND SHOWERS @ FLOOR
8. USE LISTED DRAINAGE FITTINGS FOR WATER FOUNTAIN
9. PROVIDE MIN. 1 ROOM THAT IS TYPE A ACCESSIBLE
10. EMERGENCY EGRESS LIGHTING & EXIT SIGNS REQUIRED
04/23/2007 CERTIFICATE OF OCCUPANCY Not ready for Inspection IVRS - Inspection :*
1. 5-WATER HEATERS NEED RIGID COPPER LINES INST. FROM T&P VALVE TO DUMP LINE.
2. HEAT PUMP AT EAST WING ON SOUTH END NOT WORKING REPAIR OR REPLACE
3. REMOVE OUTSIDE SCREEN FROM UNIT A-14 BEDROOM WINDOW.
4. REPAIR ELECT. FLEX LINE TO HEAT PUMP ON WEST WING MIDDLE UNIT AND NUMBER ALL HEAT PUMPS.